SOCLA Stabilisers

SOCLA Stabilisers are control valves engineered to maintain consistent downstream pressure in fluid systems, regardless of upstream pressure fluctuations or varying downstream demand. The C101 model, for instance, ensures a constant preset reduced downstream pressure, enhancing system stability and performance. These valves are suitable for applications in water distribution, irrigation, and pump outlet systems, providing reliable pressure regulation to optimise operational efficiency.

SOCLA C101 Control Valves

Pressure Reducing Valves

The SOCLA C101 Control Valve is designed for maintaining a constant preset downstream pressure, regardless of variations in upstream pressure or demand. With operating temperatures from -10°C to 90°C and pressures up to 25 bar, it is compatible with clear water systems. Available in flanged connections for DN 40–300 and threaded F/F for DN 1½, the valve complies with PED 2014/68/UE standards. Its ductile iron body with epoxy coating ensures durability in diverse applications.

 Technical Datasheet  Mounting Instructions

Pressure: PFA 10 ... 25 Bar
Size Range: 40 ... 300 mm
Body Materials: EPDM, Polyamide, Brass, Stainless Steel, Ductile Iron, & Chromed Brass
Approvals: ACS, SCP, & CE Marking
Weight Range (KG): 8 ... 328
Enquire Here

SOCLA C101C Control Valves

Pressure Reducing Valves

The SOCLA C101C Control Valve ensures consistent downstream pressure by reducing and stabilising it below upstream levels, even with fluctuating demand or upstream pressure. Equipped with an integrated check valve function, it operates efficiently at pressures up to 25 bar and temperatures from -10°C to 90°C. Suitable for clear water applications, it supports flanged or threaded connections and complies with PED 2014/68/UE standards for reliable performance in varied installations.

 Technical Datasheet  Mounting Instructions

Pressure: PFA 10 ... 25 Bar
Size Range: 40 ... 300 mm
Body Materials: EPDM, Polyamide, Brass, Stainless Steel, Ductile Iron, & Chromed Brass
Approvals: ACS, & CE Marking
Weight Range (KG): 8 ... 328
Enquire Here

SOCLA C102 Control Valves

Pressure Reducing Valves

The SOCLA C102 Control Valve stabilises downstream pressure in water distribution, irrigation, and pump outlet systems, even during variable upstream pressure or demand. Equipped with two identical pilot valves for uninterrupted operation during maintenance, it also incorporates a check valve for backflow prevention. Operating at pressures up to 25 bar and temperatures from -10°C to 90°C, it supports flanged or threaded connections. Compliant with PED 2014/68/UE standards, it ensures efficient system performance.

 Technical Datasheet  Mounting Instructions

Pressure: PFA 10 ... 25 Bar
Size Range: 40 ... 300 mm
Body Materials: EPDM, Polyamide, Brass, Stainless Steel, Ductile Iron, & Chromed Brass
Approvals: ACS, & CE Marking
Weight Range (KG): 8 ... 328
Enquire Here

SOCLA C104 Control Valves

Combined Pressure Reducing Valves

The SOCLA C104 Control Valve ensures a preset downstream pressure while maintaining a minimum upstream pressure, unaffected by variations in demand or upstream pressure. Suitable for clear water applications, it operates at temperatures from -10°C to 90°C and pressures up to 25 bar. Available in flanged or threaded configurations, the valve includes check valves for backflow prevention and complies with PED 2014/68/UE standards. It is ideal for water distribution and irrigation systems.

 Technical Datasheet Mounting Instructions

Pressure: PFA 10 ... 25 Bar
Size Range: 40 ... 300 mm
Body Materials: EPDM, Polyamide, Brass, Stainless Steel, Ductile Iron, & Chromed Brass
Approvals: ACS, & CE Marking
Weight Range (KG): 8 ... 328
Enquire Here

SOCLA C108 Control Valves

Pressure Reducing Valves

The SOCLA C108 Control Valve is designed to maintain a preset downstream pressure, regardless of upstream variations, with the ability to fully open when upstream pressure falls below a defined level. Operating between -10°C and 90°C at pressures up to 25 bar, it features ductile iron construction with an epoxy coating and EPDM seals. Suitable for flanged or threaded connections, it complies with PED 2014/68/UE standards, making it ideal for water distribution and irrigation systems.

 Technical Datasheet Mounting Instructions

Pressure: PFA 10 ... 25 Bar
Size Range: 40 ... 300 mm
Body Materials: EPDM, Polyamide, Brass, Stainless Steel, Ductile Iron, & Chromed Brass
Approvals: ACS, & CE Marking
Weight Range (KG): 8 ... 328
Enquire Here

SOCLA C301 Control Valves

Back Pressure Valves

The SOCLA C301 Control Valve stabilises and maintains a preset upstream pressure, even with varying flow rates, preventing pump suction pressure from dropping below safety levels or exceeding pump capacity. Operating at temperatures from -10°C to 90°C and pressures up to 25 bar, it features a ductile iron body with an epoxy coating and includes a built-in non-return valve. Suitable for vertical or horizontal installations, it complies with PED 2014/68/UE standards for reliable performance.

 Technical Datasheet Mounting Instructions

Pressure: PFA 10 ... 25 Bar
Size Range: 40 ... 300 mm
Body Materials: EPDM, Polyamide, Brass, Stainless Steel, Ductile Iron, & Chromed Brass
Approvals: ACS, & CE Marking
Weight Range (KG): 8 ... 328
Enquire Here

SOCLA C306 DE Control Valves

Differential Back Pressure

The SOCLA C306 DE Control Valve maintains a constant differential pressure across installations, ensuring system stability regardless of flow variations. Designed for bypass mounting, it features a ductile iron body with epoxy coating and operates at pressures up to 25 bar and temperatures from -10°C to 90°C. It includes a built-in check valve and supports flanged and threaded connections, complying with PED 2014/68/UE standards, making it ideal for precise pressure management in water systems.

 Technical Datasheet Mounting Instructions

Pressure: PFA 10 ... 25 Bar
Size Range: 40 ... 300 mm
Body Materials: EPDM, Polyamide, Brass, Stainless Steel, Ductile Iron, & Chromed Brass
Approvals: ACS, CE Marking, & WRAS
Weight Range (KG): 8 ... 328
Enquire Here

SOCLA C306 LI Control Valves

Differential Back Pressure

The SOCLA C306 LI Control Valve ensures a constant differential pressure across an overpressure pump regardless of flow rate variations. Equipped with a check valve feature for automatic closure during backpressure, it operates at pressures up to 25 bar and temperatures from -10°C to 90°C. Suitable for flanged and threaded connections, the valve is compliant with PED 2014/68/UE standards, making it ideal for water systems requiring precise pressure stabilisation.

 Technical Datasheet Mounting Instructions

Pressure: PFA 10 ... 25 Bar
Size Range: 40 ... 300 mm
Body Materials: EPDM, Polyamide, Brass, Stainless Steel, Ductile Iron, & Chromed Brass
Approvals: ACS, CE Marking, & WRAS
Weight Range (KG): 8 ... 328
Enquire Here

Frequently Asked Questions

SOCLA Stabilisers are control valves designed to maintain a constant preset downstream pressure, regardless of variations in upstream pressure or downstream demand. They ensure stable and efficient operation in water distribution systems.

These valves operate by adjusting the flow to maintain a consistent downstream pressure. When the downstream pressure drops below the set point, the valve opens to increase flow; when it rises above the set point, the valve closes to reduce flow.

The C101 model features an EPDM-reinforced membrane, a brass and stainless steel position indicator with purge, and a ductile iron body with epoxy coating. It operates effectively within a temperature range of -10°C to 90°C.

SOCLA Stabilisers are suitable for water distribution, irrigation systems, and pump outlets. They are ideal for applications requiring precise downstream pressure control.

SOCLA offers stabilisers in sizes ranging from DN 40 to DN 300 mm, with various pressure ratings to accommodate different system requirements.

Installation involves placing the valve horizontally with the cap oriented upwards (up to a 45° incline). It's recommended to install a strainer upstream and an air relief valve downstream or at the system's high point.

Regular maintenance every 6 to 12 months includes purging the upper chamber, flushing infrequently used valves, and checking and cleaning filters. A comprehensive inspection every 5 years is advisable.

Yes, models like the C102 are equipped with two identical pilot valves, allowing uninterrupted operation during maintenance or pressure setting adjustments.

Components include an EPDM-reinforced membrane, brass and stainless steel position indicators, and a ductile iron body with epoxy coating, ensuring durability and corrosion resistance.

SOCLA Stabilisers comply with international standards, including Directive 2014/68/EU, and have approvals such as ACS and PED 2014/68/EU.

They are designed for use with clear water up to 2 mm in particle size. For other fluids, it's essential to validate the operating conditions.

Yes, SOCLA Stabilisers adhere to European standards and regulations, including CE marking, ensuring reliability and compatibility in various water management applications.

FAQ

Request more information or Advice

Please feel free to request information and advice using the form below or call us on 0151 547 1221